+998 97 771 11 83 Downloads For state customers

Searches models, solutions, projects and pages. For example:

Illuminance norms by facility type: one summary table

Warehouse 50-300 lx, production hall 200-500, street 4-15, car park 50, fuel station 75, shop 300-500, sports hall 300: one ShNK 2.01.05-24 table with references and links to the solutions.

Illuminance norms by facility type: one summary table. Sila Sveta
Contents
  1. Summary table
  2. How to use the table
  3. What the table does not cover
  4. Frequently asked questions

Short answer: under ShNK 2.01.05-24 a warehouse is lit from 50 lx on the floor to 300 lx at sorting, a production hall to 200-500 lx by task category, a street to 4-15 lx or 0.3-1.0 cd/m² by category, an enclosed car park to 50 lx, a fuel station under its canopy to 75 lx, a sales floor to 300-500 lx and a sports hall to 300 lx. Below is one table with the references, and the links lead to a full analysis of each facility type.

ShNK 2.01.05-24 “Tabiiy va sunʼiy yoritish” is the current Uzbek town-planning norm for lighting: Ministry of Construction order No. 1/2-68 of 26 September 2024, registered by the Ministry of Justice under No. 309 of 25 October 2024. The text is published on lex.uz (document 7218587) in Uzbek. The values were checked against the text on 17 September 2026; check them against the current edition before announcing a procurement.

Summary table

Facility Norm Plane ShNK reference Details
Warehouse: storage zone / racks / receiving and dispatch / sorting 50 / 75 / 200 / 300 lx floor; vertical; H-0.8 Annex 9, Table 2, items 65, 70 Warehouses
Production hall: medium-precision work (IV) / high precision (III) 200-300 / 200-500 lx H-0.8 Annex 1, Table 1 Production halls
Production hall: fitting and mechanical bays 500 lx H-0.8 Annex 9, Table 2, item 23 Production halls
Category B street 0.6-1.0 cd/m² or 10-15 lx surface Table 15 Streets
Category V service roads 0.3-0.4 cd/m² or 4-6 lx surface Table 15 Streets
Enclosed car park, storage places / depot 50 / 75 lx floor Annex 9, Table 2, items 2b, 2a Car parks
Open lot: unheated / heated 10 / 20 lx surface Annex 9, Table 2, item 1 Car parks
Fuel station: pumps under canopy / fuelling and tank-filling places / entrances / grounds 75 / 20 / 15 / 10 lx surface Annex 9, Table 2, item 3a; Table 21 Fuel stations
Sales floor: clothes, furniture, appliances / self-service food / supermarket 300 / 400 / 500 lx, Ra at least 85 H-0.8 Annex 9, Table 1, items 78-81 Retail
Sports hall: games / school hall 300 lx and 150 lx vertical / 200 lx floor; V-2.0 Annex 9, Table 1, items 64-66, 33 Sports
Office: work rooms 300 lx H-0.8 Annex 9, Table 1, item 1 All norms
Greenhouse ShNK does not apply - introductory part Greenhouses

H-0.8 is the horizontal working plane at 0.8 m, H-0.0 the floor or surface, V a vertical plane at the stated height. 50 lx on the floor and 75 lx on the rack are different requirements for one warehouse, which is why the table keeps them apart.

How to use the table

  • The norm is set for the whole service life of the installation, not for the day it is commissioned. That is why the maintenance factor MF enters the calculation (Annex 1, Table 3): 0.67-0.71 for clean halls, 0.71 for sales floors and offices, 0.63-0.67 for streets.
  • In a production hall the norm is set per area: one bay can hold areas of different classes.
  • The scale of normalised illuminance is set by item 5: 20, 30, 40, 50, 75, 100, 125, 200, 300, 400, 500, 600, 750, 1000 lx and so on. Values such as “250 lx” are not in the norm; take the nearest step of the scale.
  • If the client’s specification asks for more than the norm, the design follows the specification, but never goes below the norm.

What the table does not cover

  • Greenhouses and rooms for plants are excluded from the scope of ShNK. Light for people in the aisles is set by the specification, and grow lighting is calculated in PAR by agronomy.
  • The norm excludes sports venues as such from its scope: competition and broadcasting levels are set by the federation rules and the broadcaster. EN 12193 works as a reference, but it is not a norm of Uzbekistan.
  • Values for a production hall depend on the task category, so there is no “single figure for a hall”. The full table with Kp, UGR and Ra is in the article Illuminance norms ShNK 2.01.05-24 by facility type.

Specification templates with these norms for six facility types are on the public customers page. We calculate to the norm for your plan free of charge: request a calculation.

Frequently asked questions

What is the illuminance norm for a warehouse?

50 lx on the floor in the storage zone and 75 lx on the racks in the vertical plane, 200 lx at receiving and dispatch, 300 lx at sorting (Annex 9, Table 2, items 65, 70).

Is street illuminance set in lux or in cd/m²?

The norm sets the average road surface luminance in cd/m² and gives illuminance in lux as an alternative (Table 15). For a category B street that is 0.6-1.0 cd/m² or 10-15 lx, depending on traffic.

Is there an illuminance norm for a greenhouse?

No. Rooms for plants are excluded from the scope of ShNK 2.01.05-24; the specification sets the norm for light for people, and grow lighting is calculated in PAR by agronomy.

All articles

One more article

IES file and DIALux: check a luminaire before you buy

What an IES file holds under LM-63, how to tell a module file from a luminaire file, load it into DIALux evo and what to check: flux, power, light distribution curve, utilisation factor.

We will calculate your site

A DIALux calculation with isolux contours, a bill of materials and payback. Free and with no obligation.

Get a calculation Savings calculator